5.0 BMCS ACCESS
The Enmet CAP's (Central Access Panels or Scanners) may be accessed via an RS-485 link using the
Modbus protocol. Up to 28 CAP units may be connected on a single network – in this case only 2 are
connected.
The BMCS acts as a Modbus master.
5.1 SETUP
Each CAP unit must be given a unique Address so it can be specifically be accessed by the BMCS. This
is done as follows:
Press the Setup key on the CAP keypad.
Press 3 for Cap Configuration.
Press 3 for CAP Net Address.
Enter the desired Address. This value is typically already set at the factory starting at 1 and
increasing incrementally for additional CAP units in the system.
5.2 SERIAL CONFIGURATION
2 Wire RS-485 (1/2 Duplex)
9600 Baud, Even parity, 8 Data bits, 1 stop bit.
For connection to a PC, an RS-485 to RS-232 converter module may be used. This module plugs into
the PC’s serial port and provides a 2 wire RS-485 connection. For convenience, a port-powered
converter should be used.
The following RS-485-232 converter has been tested with the system:
Model: 485SD9TB (Manufacturer: B&B Electronics )
5.3 MODBUS ACCESS REGISTERS
The Enmet CAP is a Read Only device i.e. the BMCS can only read, but not modify information in the
CAP.
5.3.1 MODBUS COMMANDS SUPPORTED
Read Holding Registers (Modbus command # 3)
Other modbus commands are NOT supported.
5.3.2 REGISTER MAP
The main information intended for the BMCS is the highest ppm concentration read
by the CAP from any EC Gold transmitters networked to it. This information is used
by the BMCS to control the ventilation fan speed.
This MAX PPM value is in IEEE754 format, which is 4 bytes or 2 consecutive
modbus registers. The packing is as follows:
Floating point value (before transmission):
Byte 3 (Most Sig. Byte) Byte 2 Byte 1 Byte 0 (Least Sig. Byte)
As Sent: (First to last): Byte 1, Byte 0, Byte 3, Byte 2.
i.e. Byte 1 is sent first followed by Byte 0, then Byte 3 and finally Byte 2.
If 2
nd
second serial port is purchased, see attached “Scanner Modbus MAP”